Responce LetterAdaptive Architecture 20111 Stevens Creek Blvd, Suite 270 Tel: (408) 865-1089 Cupertino, CA 95014 Email: info@adaptivearch.us September 12, 2019 City of Campbell 70 North First St Campbell, CA 95008 Re: Response to Development Review Comments (Planning No. PLN2019-50) Project: 1625 W Campbell Ave, Springbridge Preschool Dear staff of City of Campbell: Thank you for reviewing the proposed preschool project. Below are the responses to your comments received on March 14, 2019 Fire Department Comments: 1.Review of this Developmental proposal is limited to acceptability of site access, water supply, and may include specific additional requirements as they pertain to fire department operations, and shall not be construed as a substitute for formal plan review to determine compliance with adopted model codes. Prior to performing any work, the applicant shall make application to, and receive from, the Building Department all applicable construction permits. Response: Noted, and no construction work is proposed with this application. 2.Plans indicate a fully sprinklered E occupancy with an approved fire alarm system throughout. Verify annual maintenance. Response: See attached photo of sprinkler annual test date of Sept. 2019. 3.Children ages 2 through and including second-grade pupils shall not be located above or below the first story. [CFC, Ch4, 452.1.4]. Review of the plans does not indicate this site qualifies for any exceptions to this requirement. Provide qualifying details or indicate age groups that will comply. Response: In the original 2017 T.I. permit, we had used exception 2 under CFC 452.1.4: In buildings equipped with an ​automatic sprinkler system​ throughout, rooms used for kindergarten, first- and second-​grade​ children or for ​day-care purposes may be located on the second ​story​, provided there are at least two exterior ​exit​ doors, or other egress systems complying with ​Section 1018​ with two ​exits​, for the exclusive use of such occupants. Egress systems for the Page 1 of 2 exclusive use of such occupants shall be maintained until ​exit discharge​ at grade​ is attained. This exception applies here because the building is fully sprinklered and and we created an 1-hour rated corridor which led to two exit stairways that can exit directly to the exterior. The age group of children is indicated on sheet A0.2, under code analysis note ‘D’ and general notes on floor plan sheet A2.1. 4.Provide portable fire extinguishers (minimum type of 2A-10BC) for every 75 ft. of travel distance or 3000 sq. ft. (per unit of A) CFC 906.3. Verify annual maintenance. Response: See photos of fire extinguishers’ purchase date attached. All new extinguishers were purchased on 2/27/19. Building Inspection Division Comments: 1.TITLE 24 ACCESSIBILITY - COMMERCIAL: This project shall be in full compliance with california access laws. (This comment was issued under the first Planning application. An Elevator should be installed to make the second floor fully accessible.) Response: Per discussion with Building Official, the building has been evaluated by two CASp certified compliance experts. Please see attached reports prepared by Marx/Okubo Associates and United Spinal Association. Public Works Comments: 1.The original Conditional Use Permit (PLN2014-301) that established this school included Public Works Department Conditions of Approval that the Applicant has failed to satisfy. The two existing project driveways along West Campbell Avenue were required to be upgraded to ADA compliant driveways prior to occupancy of the school. Until the applicant satisfies the previous Conditions of Approval, Public Works deems this new submittal incomplete. Response: Two project driveways have been upgraded to comply with ADA per encroachment permit ENC2019-00123. Sincerely, Janice Yeh, AIA Principal Architect (408) 865-1089 Page 2 of 2