Site & Variance - Kaeding - 2005
Mareh 24, 2006 Apri119, 2006
Brent Keading
813 South McGlincy Lane
Campbell, CA 95008
Re: Building Permit No: BLD2006-288
813 Cristich Lane
Dear Applicant:
The Planning Division has reviewed your building plan permit submittal for the construction of an
industrial building at the above referenced address. Per the Conditions of Approval for Variance
PLN2005-145 and Site and Architectural Review PLN2005-144, please review the following notes and
address the action items prior to issuance of a building permit:
Notes:
1. One office has been added to the first floor (within the approved building area) and is acceptable as
proposed as this change does not affect the parking demand.
Action Items:
2. Lot Line Adjustment:
Please complete the lot line adjustment prior to issuance of the building permit. What's the status?
3. Sheet All. Site and Landscape Plan:
a. Per Condition No.5, please specify the fencing proposed along the north property line. OK.
Wrought iron 5 feet in height, Sheet All.
b. Per Condition No.5, please specify the finish of the trash enclosure as matching the building
(stucco). OK. Plaster and color to match building added, Sheet All.
c. Per Condition No.6, no sign approval(s) has (have) been granted for this new building. Please
submit for sign approval(s) prior to erecting any signs. OK. Note on Sheet AO.
d. Per Condition No.8, please specify all exterior lighting. Sheets All and A3.2. Note color(s) of
Fixtures A and B. Provide cut sheet of Fixture C.
e. Per Condition No.9, please specify landscape irrigation. No Sheet L-I provided as noted in
applicant's response.
BLD2006-288 - 813 Cristich Lane
Page 2 of2
4. Sheet A21. Floor Plans and Roof Plan:
a. Per Condition No. 11, please specify the location and height of all proposed roof-top equipment.
(All roof-top equipment shall be screened.) Sheet A2l, Roof Plan, does not verify that (2)
proposed HVAC units will be screened. Eliminate General Note #3 - no new roof screen is
approved.
5. Sheet A3.2. Exterior Elevations:
a. Per Condition No.1, please clearly note the locations of Body Color #1 and #2 on all elevations.
OK. Noted on Sheet A32.
Thank you for the opportunity to review these plans. Please submit your revised drawings to the Building
Division. If you have any questions regarding the comments contained in this letter, please feel free to
contact me at (408) 866-2124 or by email atiackieL@cityofcampbel1.com.
Sincerely,
Jackie C. Young Lind, AICP
Senior Planner
cc: Building
Brent Keading, 813 South Cristich Lane, Campbell, CA 95008
LPMD, Debbie Hill, 2620 Augustine Drive, Suite 185, Santa Clara, CA 95054
March 24, 2006
Brent Keading
813 South McGlincy Lane
Campbell, CA 95008
Re: Building Permit No: BLD2006-288
813 Cristich Lane
Dear Applicant:
The Planning Division has reviewed your building plan permit submittal for the construction of an
industrial building at the above referenced address. Per the Conditions of Approval for Variance
PLN2005-145 and Site and Architectural Review PLN2005-144, please review the following notes and
address the action items prior to issuance of a building permit:
Notes:
1. One office has been added to the first floor (within the approved building area) and is acceptable as
proposed as this change does not affect the parking demand.
Action Items:
2. Lot Line Adjustment:
Please complete the lot line adjustment prior to issuance of the building permit.
3. Sheet All. Site and Landscape Plan:
a. Per Condition No.5, please specify the fencing proposed along the north property line.
b. Per Condition No.5, please specify the finish of the trash enclosure as matching the building
( stucco).
c. Per Condition No.6, no sign approval(s) has (have) been granted for this new building. Please
submit for sign approval(s) prior to erecting any signs.
d. Per Condition No.8, please specify all exterior lighting.
e. Per Condition No.9, please specify landscape irrigation.
70 North First Street. Campbell, California 95008-1436 . TEL 408.866.2140 . FAX 408.866.8381 . IDD 408.866.2790
of{ . CA-11 -,
. :/.><9
~ \<'
- r"'"
V r
-' ...
1- <.
<!' (.,'
O~CH 1'1t\)'
CITY OF CAMPBELL
Community Development Department
December 15, 2005
Mr. Brent Kaeding/Mr. Howard Kaeding
Kaeding Performance
813 Cristich Lane
Campbell, CA 95008
Re: PLN2005-144/145 - 813 Cristich Lane
Site and Architectural Review PermiWariance
Dear Applicant:
Please be advised that at its meeting of December 13, 2005, the Planning Commission
adopted Resolution No. 3702 approving a Site and Architectural Review Permit
(PLN2005-144) to allow the demolition of an existing residence and the construction of
a new 5,347 square foot industrial building and Resolution No. 3703 granting a Variance
to allow a building that was destroyed by fire to be rebuilt one foot from a side property
line at the above referenced property.
This action is effective in ten calendar days, unless appealed in writing to the City Clerk
by 5 p.m. on Friday, December 23, 2005. The time within which judicial review of this
action must be sought is governed by Section 1094.6 of the California Code of Civil
Procedure, unless another statute (such as California Government Code Section 65009
or some other applicable provision) sets forth a more specific time period.
If you have any questions, please do not hesitate to contact me at (408) 866-2140.
Sincerely,
Jackie C. Young Lind
Senior Planner
cc: Debbie HiII/LPMD Architects (Project Architect)
2620 Augustine Drive, Suite 185
Santa Clara, CA 95054
Frank Mills, Building
Chris Veargason, Fire
Ed Arango, Public Works
70 North First Street. Campbell, California 95008-1436 . TEL 408.866.2140 . FAX 408.866.8381 . TDD 408.866.2790
BLD2006-288 - 813 Cristich ..Ie
Page 2 of2
4. Sheet A21. Floor Plans and Roof Plan:
a. Per Condition No. 11, please specify the location and height of all proposed roof-top equipment.
(All roof-top equipment shall be screened.)
5. Sheet A3.2. Exterior Elevations:
a. Per Condition No.1, please clearly note the locations of Body Color #1 and #2 on all elevations.
Thank you for the opportunity to review these plans. Please submit your revised drawings to the Building
Division. If you have any questions regarding the comments contained in this letter, please feel free to
contact me at (408) 866-2124 or by email atiackieL@citvofcampbell.com.
Sincerely,
Jackie C. Young Lind, AICP
Senior Planner
cc: Building
Brent Keading, 813 South Cristich Lane, Campbell, CA 95008
LPMD, Debbie Hill, 2620 Augustine Drive, Suite 185, Santa Clara, CA 95054
--..,
RESOLUTION NO. 3702
BEING A RESOLUTION OF THE PLANNING COMMISSION OF THE
CITY OF CAMPBELL APPROVING A SITE AND ARCHITECTURAL
REVIEW PERMIT (PLN2005-144) TO ALLOW THE DEMOLITION OF
AN EXISTING RESIDENCE AND THE CONSTRUCTION OF A NEW
5,347 SQUARE FOOT INDUSTRIAL BUILDING ON PROPERTY
OWNED BY MR. HOWARD KAEDING LOCATED AT 813 CRISTICH
LANE IN AN M-1-S (LIGHT INDUSTRIAL) ZONING DISTRICT.
APPLICATION OF MR. BRENT KAEDING, ON BEHALF OF
KAEDING PERFORMANCE. PLN2005-144.
After notification and public hearing, as specified by law and after presentation by the
Community Development Director, proponents and opponents, the hearing was closed.
After due consideration of all evidence presented, the Planning Commission did find as
follows with respect to application PLN2005-144:
1. The project is consistent with the development standards and design guidelines set
forth in the General Plan in that project eliminates a nonconforming residence,
redevelops a site in the McGlincy neighborhood, provides landscaping and
screening, and utilizes high-quality, finished construction materials.
2. Subject to compliance with conditions of approval requiring a conforming south side
yard setback and landscape buffer, the proposed project is consistent with the
development standards prescribed for the M-1 (Light Industrial) Zoning District (i.e.
minimum setbacks, height restriction, floor area ratio, and parking requirements).
3. The project consists of a 5,347 square foot warehouse/industrial building, with a
Floor Area Ratio of 0.36, where the maximum floor area ratio is 0.40.
4. The project provides sixteen parking spaces where a minimum of sixteen parking
spaces are required.
5. The proposed project as conditioned is well designed and is architecturally
compatible with the surrounding neighborhood, and with the redevelopment
expectations prescribed by the General Plan. The building is well articulated and
considers the design of all elevations, with particular attention to the Crjstich Lane
streetscape and the view shed from Highway 17.
6. The proposed project does not include the removal of any protected trees.
7. The proposed project is surrounded by industrial to the north, south and east; and
Highway 17 to the west.
8. The project qualifies as Categorically Exempt under Section 15303(c) of the
California Environmental Quality Act (CEQA), pertaining to New Construction of
Small Structures in an urbanized area.
Planning Commission Kt:solution No. 3702
PLN2005-144 - 813 Cristich Lane -- Site and Architectural Review Permit
Page 2
Based upon the foregoing findings of fact, the Planning Commission further finds and
concludes that:
1. The development will be compatible with the General Plan of the City and will aid in
the harmonious development of the immediate area.
2. The development will be compatible with the Zoning Code of the City.
3. No substantial evidence has been presented from which a reasonable argument
could be made that shows that the project, as currently presented and subject to the
required conditions of approval, will have a significant adverse impact on the
environment.
4. The proposed development will not be detrimental to the health, safety or welfare of
the neighborhood or the City as a whole.
5. There is a reasonable relationship between the use of the fees imposed upon the
project and the type of development project.
6. There is a reasonable relationship and a rough proportionality between the
conditions of approval and the impacts of the project.
THEREFORE, BE IT RESOLVED that the Planning Commission approves a Site and
Architectural Review Permit (PLN2005-144) to allow the demolition of an existing
residence and the construction of a new 5,347 square foot industrial building on
property owned by Mr. Howard Kaeding located at 813 Cristich Lane in an M-1-S
(Light Industrial) Zoning District, subject to the following conditions:
Where approval by the Director of Community Development, City Engineer, Public
Works Director, City Attorney or Fire Department is required, that review shall be for
compliance with all applicable conditions of approval, adopted policies and guidelines,
ordinances, laws and regulations and accepted engineering practices for the item under
review. Additionally, the applicant is hereby notified that he/she is required to comply
with all applicable Codes or Ordinances of the City of Campbell and the State of
California that pertain to this development and are not herein specified.
COMMUNITY DEVELOPMENT DEPARTMENT
Plannina Division:
1. Approved Proiect: Approval is granted for a Site & Architectural Review (PLN2004-
144) to construct a warehouse/industrial building at 813 Cristich Lane. The
proposed project shall substantially conform to the project exhibits listed below,
except as may be modified by the Conditions of Approval herein:
Planning Commission ~vsolution No. 3702
PLN2005-144 -- 813 Cristich Lane - Site and Architectural Review Permit
Page 3
a. Set of plans prepared by LPMD Architects, received on December 5, 2005,
including building site and landscape plan, floor plans and roof plan, elevations
and preliminary grading and drainage.
b. Color samples submitted by LPMD Architects, received on December 5, 2005.
2. Site & Architectural Review Aooroval Exoiration: The Site & Architectural approval
shall be valid for one year from the date of final approval. Within this one-year
period a building permit must be obtained and construction completed one year
thereafter, or the Site & Architectural Review shall be void.
3. Revocation of Permit: The approved, primary use is a warehouse for parts for high
performance race cars. Given the specialty nature of the product, the on site "sales"
function more as "distribution". No auto repair, fabrication, finishing, assembly,
augmentation, etc. is approved for this site. Changes to the approved use require
review and approval by the Planning Commission. Operation of the use in violation
of the Site and Architectural Review or any standards, codes, or ordinances of the
City of Campbell shall be grounds for consideration of revocation of the Site and
Architectural Review by the Planning Commission.
4. Fencina. Walls and Trash Enclosure: All new fencing/walls shall comply with
Section 21.18.060 of the Campbell Municipal Code. The design of, and the
materials and colors for the fencing, walls and trash enclosure shall be reviewed and
approved by the Community Development Director prior to issuance of a building
permit.
5. Sianaae: No signageis approved as part of the development applications approved
herein. No sign shall be installed until a Sign Permit is approved as specified in the
Sign Ordinance.
6. Parkina and Drivewavs: All parking and driveway areas shall be developed in
compliance with the approved plans and Chapter 21.28 (Parking and Loading) of the
Campbell Municipal Code.
7. On-Site Liahtina: On-site lighting shall be shielded away from adjacent properties
and directed on site. The design, type, intensity and location of any proposed
exterior lighting for the project shall be reviewed and approved by the Community
Development Director prior to installation of the lighting for compliance with all
applicable Conditions of Approval, ordinances, laws and regulations. Lighting
fixtures shall be of a decorative design to be compatible with the industrial
development and shall incorporate energy saving features.
8. Landscaoe Plan: Prior to the issuance of building permits, the applicant shall submit
a final detailed landscape and irrigation plan to the Planning Division for review and
approval by the Community Development Director. The landscape and irrigation plan
Planning Commission hvsolution No. 3702
PLN2005-144 - 813 Cristich Lane -- Site and Architectural Review Permit
Page 4
shall substantially conform to the approved conceptual landscape plan and the City's
Water Efficient Landscaping Standards (WELS).
· All landscaping and trees shall be installed prior to the issuance of a Certificate of
Occupancy for the building.
· Minimum tree size of 15 gallon trees shall be provided.
9. Utilities: All new on-site utilities shall be installed underground per section 21.18.140
of the Campbell Municipal Code.
10. Screenina: Screening of all roof-top equipment shall be shown on the plans
submitted for a building permit with a building cross section. The placement on site
of any required utility equipment (Le., back-flow preventors, transformers, etc.) shall
be reviewed and approved by the Community Development Director prior to
issuance of a building permit.
11. Paint Color: The approved paint colors shall be field-verified by the Community
Development Director.
12. Contractor Contact Information Postina: The project site shall be posted with the
name and contact number of the lead contractor in a location visible from the public
street prior to the issuance of building permits.
13. Construction Hours: Construction activities will be limited to the hours of 8:00 a.m.
to 5:00 p.m. weekdays and 9:00 a.m. to 4:00 p.m. Saturdays. Construction is
prohibited on Sundays and Holidays, unless an exception is granted by the Building
Official.
14. Hours: Construction activities will be limited to the hours of 8:00 a.m. to 5:00 p.m.
weekdays and 9:00 a.m. to 4:00 p.m. Saturdays. Construction is prohibited on
Sundays and Holidays, unless an exception is granted by the Building Official.
15. Prooertv Maintenance: The property is to be maintained free of any combustible
trash, debris and weeds until the time that actual construction commences. All
existing structures shall be secured by having the windows boarded up and doors
sealed shut, or shall be demolished or removed from the property (Section 11.201
and 11.414, 1985 Ed. Uniform Building Code).
16. Outdoor StoraQe: No outdoor storage or outdoor overnight parking is permitted on
the subject property. No equipment, materials or business vehicles shall be parked
and/or stored outside the building or within the parking lot.
Planning Commission Resolution No. 3702
PLN2005-144 -- 813 Cristich Lane - Site and Architectural Review Permit
Page 5
17. Outdoor Displav: No outdoor display is permitted on the subject property. All stock
for sale shall be kept and displayed inside the buildings. All exterior parking spaces
shall be used only for employees and/or customer use.
18. Buildina Modifications: Prior to any changes or modifications to the building or floor
plan the applicant shall submit proposed plans to the Community Development
Department for review an approval.
Buildina Division:
19. Permits Reauired: A building permit application shall be required for the proposed
new commercial structure. The building permit shall include
Electrical/Plumbing/Mechanical fees when such work is part of the permit.
20. Construction Plans: The Conditions of Approval shall be stated in full on the cover
sheet of construction plans submitted for building permit.
21. Size of Plans: The minimum size of construction plans submitted for building
permits shall be 24 in. by 36 in.
22. Plan Preoaration: This project requires plans prepared under the direction and
oversight of a California licensed Engineer or Architect. Plans submitted for building
permits shall be "wet stamped" and signed by the qualifying professional person.
23. Site Plan: Application for building permit shall include a competent site plan that
identifies property and proposed structures with dimensions and elevations as
appropriate. Site plan shall also include site drainage details. Site address and
parcel numbers shall also be clearly called out. Site parking and path of travel to
public sidewalks shall be detailed. Site plan shall also clearly call out location of a
permanent elevation bench mark.
24. Soils Reoort: Two copies of a current soils report, prepared to the satisfaction of the
Building Official, containing foundation and retaining wall design recommendations
shall be submitted with the building permit application. This report shall be prepared
by a licensed engineer specializing in soils mechanics.
25. Foundation Inspections: A pad certificate prepared by a licensed civil engineer or
land surveyor shall be submitted to the project building inspector upon foundation
inspection. This certificate shall certify compliance with the recommendations as
specified in the soils report and the building pad elevation and on-site retaining wall
locations and elevations are prepared according to approved plans. Horizontal and
vertical controls shall be set and certified by a licensed surveyor or registered civil
engineer for the following items:
Planning Commission Rt::solution No. 3702
PLN2005-144 -- 813 Cristich Lane -- Site and Architectural Review Permit
Page 6
a. pad elevation
b. finish floor elevation (first floor)
c. foundation comer locations
26. Title 24 EnerQY Compliance: California Title 24 Energy Standards Compliance
forms shall be blue-lined on the construction plans. Compliance with the Standards
shall be demonstrated for conditioning of the building envelope and lighting of the
building.
27. Speciallnsoections: When a special inspection is required by U.B.C. Section 1701,
the architect or engineer of record shall prepare an inspection program that shall be
submitted to the Building Official for approval prior to issuance of the building
permits, in accordance with U.B.C Section 106.3.5. Please obtain City of Campbell,
Special Inspection forms from the Building Inspection Division Counter.
28. Stormwater: The City of Campbell, standard Santa Clara Valley Non-point Source
Pollution Control Program specification sheet shall be part of plan submittal. The
specification sheet (size 24" X 36") is available at the Building Division service
counter.
29. Title 24 Accessibility - Commercial: On site general path of travel shall comply with
the latest California Title 24 Accessibility Standards. Work shall include but not be
limited to accessibility to building entrances from parking facilities and sidewalks.
30. Title 24 Accessibility - Commercial: Projects seeking to use the Title 24 Hardship
exemption clause shall blue-line completed, City of Campbell "20%" exemption form
on submitted construction plans. Form is available at Building Division service
counter.
31. Approvals ReQuired: The project requires the following agency approval prior to
issuance of the building permit:
a. West Valley Sanitation District
b. Santa Clara County Fire Department
c. School District:
i) Campbell Union School District (378-3405)
ii) Campbell Union High School District (371-0960)
iii) Moreland School District (874-2900)
iv) Cambrian School District (377-2103)
d. Bay Area Air Quality Management District (Demolitions Only)
32. P, G.& E.:Applicant is advised to contact Pacific Gas and Electric Company as early
as possible in the approval process. Service installations, changes and/or
relocations may require substantial scheduling time and can cause significant delays
Planning Commission kv$olution No. 3702
PLN2005-144 -- 813 Cristich Lane -- Site and Architectural Review Permit
Page 7
in the approval process. Applicant should also consult with P.G. and E. concerning
utility easements, distribution pole locations and required conductor clearances.
FIRE DEPARTMENT
33. Required Fire Flow: The fire flow for this project is 2,000 gpm at 20 psi residual
pressure. The adjusted fire flow is available from area water mains and fire
hydrant(s) which are spaced at the required spacing.
34. Fire Apparatus (Enaine) Access Roads Required: Provide access roadways with a
paved all weather surface, a minimum unobstructed width of 20 feet, vertical
clearance of 13 feet 6 inches, minimum circulating turning radius of 36 feet outside
and 23 feet inside, and a maximum slope of 15%. Installations shall conform with
Fire Department Standard Details and Specifications sheet A-1.
35. Fire Lane Markina Reauired: Provide marking for all roadways within the project.
Markings shall be per fire department specifications. Installations shall also conform
to Local Government Standards and Fire Department Standard Details and
Specifications A-6.
PUBLIC WORKS DEPARTMENT
36. LeQal Lot: The applicant shall provide documentation to ascertain that the property
has been legally created.
37. Preliminarv Title Report: Prior to issuance of any grading or building permits for the
site, the applicant shall provide a current Preliminary Title Report.
38. Irrevocable Offer of Dedication for Public Street Purposes: Prior to issuance of any
grading or building permits for the site, the applicant shall make an irrevocable offer
of dedication in fee simple for additional right-of-way for public street purposes along
the Cristich Lane frontage to accommodate a 30 foot half street width and a 10 foot
Public Utility Easement. The applicant shall submit the necessary documents for
approval by the City Engineer, process the submittal with City staffs comments and
fully complete the right-of-way process. The applicant shall cause all documents to
be prepared by a registered civil engineer/land surveyor, as necessary, for the City's
review and recordation.
39. Deferred Street Improvement Aareement: Prior to issuance of any grading,
drainage, or building permits for the site, the owner shall execute a deferred street
improvement agreement for construction of standard street improvements, as
required by the City Engineer. The future plans for the deferred street improvement
shall include the following:
Planning Commission kt;solution No. 3702
PLN2005-144 -- 813 Cristich Lane -- Site and Architectural Review Permit
Page 8
a. Show location of all existing utilities within the new and existing public right of
way.
b. Relocation of all existing utilities including utility boxes, covers, poles, etc. outside
of sidewalk area. No utility boxes, covers, etc. will be allowed in the sidewalk
area.
c. Removal of existing street section to centerline.
d. Installation of engineered structural pavement section to centerline, as required
by the City Engineer.
e. Installation of standard curb, gutter, sidewalk and ADA compliant driveway
approaches.
f. Installation of street trees, tree wells and irrigation at 30 feet on center.
g. Installation of streetlights, conduits, conductors and related facilities in
accordance with the City of Campbell's Street Lighting Policies.
h. Installation of traffic control, signage, and markings.
i. Construction of conforms to existing public and private improvements, as
necessary.
40. Water Meter{s) and Sewer Cleanout{s): Existing and proposed water meter(s) and
sewer cleanout(s) shall be relocated or installed on private property behind the
future public right-of-way line.
41. Utilities: All on-site utilities shall be installed underground per Section 21.18.140 of
the Campbell Municipal Code for any new or remodeled buildings or additions.
Applicant shall comply with all plan submittals, permitting, and fee requirements of
the serving utility companies.
42. Utilitv Coordination Plan: Prior to issuance of building permits for the site, the
applicant shall submit a utility coordination plan and schedule for approval by the
City Engineer for installation and/or abandonment of all utilities. The plan shall
clearly show the location and size of all existing utilities and the associated main
lines; indicate which utilities and services are to remain; which utilities and services
are to be abandoned, and where new utilities and services will be installed. Joint
trenches for new utilities shall be used whenever possible.
43. Pavement Restoration: Based on the utility coordination plan, the applicant shall
prepare a pavement restoration plan for approval by the City Engineer prior to any
utility installation or abandonment. Public Streets that have been reconstructed or
overlaid within the previous five years will require boring and jacking for all new utility
installations. Cristich Lane is currently a private street.
44. Gradina and Drainaae Plan: Prior to issuance of any grading or building permits for
the site, the applicant shall conduct hydrology studies based on a ten-year storm
frequency, prepare an engineered grading and drainage plan, and pay fees required
to obtain necessary grading permits. The plans shall comply with the 1998 edition of
Planning Commission K~solution No. 3702
PLN2005-144 - 813 Cristich Lane -- Site and Architectural Review Permit
Page 9
the California Building Code including Chapters 10, 11, 18, 33, and Appendix
Chapter 33.
45. Storm Drain Area Fee: Prior to issuance of any grading or building permits for the
site, the applicant shall pay the required Storm Drain Area fee, currently set at
$2,650 per net acre, which is $927.00.
46. Stormwater Pollution Prevention Measures: Prior to issuance of any grading or
building permits, the applicant shall comply with the National Pollution Discharge
Elimination System (NPDES) permit requirements, Santa Clara Valley Water District
requirements, and the Campbell Municipal Code regarding stormwater pollution
prevention. Specifically the project must include source control, site design and
treatment measures to achieve compliance with Provision C.3. of the NPDES
Permit. Measures may include, but are not limited to, minimization of impervious
surface area, vegetated swales, infiltration areas, and treatment devices. The
primary objectives are to improve the quality and reduce the quantity of stormwater
runoff to the bay.
Resources to achieve these objectives include Storm water Best Management
Practices Handbook for New Development and Redevelopment ("CA BMP
Handbook") by the California Stormwater Quality Association (CASQA), 2003; Start
at the Source: A Design Guidance Manual for Storm water Quality Protection ("Start
at the Source") by the Bay Area Stormwater Management Agencies Association
(BASMAA), 1999; and Using Site Design Techniques to Meet Development
Standards for Storm water Quality: A Companion Document to Start at the Source
("Using Site Design Techniques") by BASMAA, 2003.
a. Upon submission of the plans, the applicant shall calculate and submit to the City
the amount of impervious surface created or replaced by the development.
b. Upon submission of the grading and drainage plan, the applicant's designer or
engineer shall also submit the required certification for sizing, selection, and
preliminary design of treatment BMP's for the project site to meet the
requirements of the City of Campbell's NPDES permit, No. 01-119, Provision
C.3.
c. The applicant shall also comply with any other or new conditions as required by
the City of Campbell's most current NPDES permit.
47. Operation and Maintenance of Stormwater Pollution Prevention Measures: Prior to
issuance of the building permit, the applicant shall execute an agreement and
provide security for the operation and maintenance of stormwater pollution
prevention measures installed or provided as a part of this project.
Prior to allowing occupancy for any and/or all buildings, the applicant shall:
Planning Commission Resolution No. 3702
PLN2005-144 -- 813 Cristich Lane -- Site and Architectural Review Permit
Page 10
a. Have a qualified BMP certifier inspect the stormwater management facilities,
submit a complete set of as-built drawings to Public Works Engineering, and
certify on these drawings that:
i. The stormwater management facilities were constructed in compliance with
approved plans;
ii. The as-built drawings show all pertinent constructed dimensions, elevations,
shapes, and materials;
Hi. All variations in construction from the approved design plan have been
identified, including omissions to and additions from the approved plan; and
iv. Any changes are in conformance with local, state, or federal regulations.
b. Sign the "Covenants for the Operation and Maintenance of Stormwater
Facilities".
PASSED AND ADOPTED this 13th day of December, 2005, by the following roll call
vote:
AYES:
NOES:
ABSENT:
ABSTAIN:
Alderete, Ebner, Francois, Gibbons and Roseberry
Doorley
None
Rocha
APPROVED:~Y~ lJf td
Iza eth Gibbons, Chair
~y~
Commissioners:
Commissioners:
Commissioners:
Commissioners:
ATTEST:
Sharon Fierro, Secretary
RESOLUTION NO. 3703
BEING A RESOLUTION OF THE PLANNING COMMISSION OF THE
CITY OF CAMPBELL GRANTING A VARIANCE (PLN2005-145) TO
ALLOW A BUILDING THAT WAS DESTROYED BY FIRE TO BE RE-
BUILT ONE FOOT FROM A SIDE PROPERTY LINE ON PROPERTY
OWNED BY MR. HOWARD KAEDING LOCATED AT 813 CRISTICH
LANE IN AN M-1-S (LIGHT INDUSTRIAL) ZONING DISTRICT.
APPLICATION OF MR. BRENT KAEDING, ON BEHALF OF
KAEDING PERFORMANCE. PLN2005-145.
After notification and public hearing, as specified by law and after presentation by the
Community Development Director, proponents and opponents, the hearing was closed.
After due consideration of all evidence presented, the Planning Commission did find as
follows with respect to application PLN2005-145:
1. The proposed project consists of the demolition of an existing residence and the
construction of a new, 8,014 square foot warehouselindustrial building on a site
where a previous industrial building was destroyed by fire.
2. The proposed building is 5,347 square feet (including a 420 square foot mezzanine),
and the parcel is 14,888 net square feet in area. The Floor Area Ratio (FAR) of the
proposed building is .36, where a maximum of .40 is allowable. The height of the
proposed building is 24'-6", where a maximum of 45'-0" is allowable. The proposed
landscape cover is 13%, where a minimum of 8% is required.
3. The proposed siting of the building would require approval of a Variance to reduce
the south side yard setback from 12'-3" to 1 '-0". The required side yard setback in
the M-1 zoning district is 5 feet, or one-half the height if the building wall adjacent to
the side property line, whichever is greater. The building height is 24'-6", therefore
the minimum, required side yard setback is 12'-3". The setback would create an
area that is difficult to maintain.
4. The subject property is long and narrow and constrained due to Highway 17 and
Cristich Lane dedications.
Based upon the foregoing findings of fact, the Planning Commission further finds and
concludes that:
1. The strict or literal interpretations and enforcement of the specified regulation(s)
would result in a practical difficulty or unnecessary physical hardship inconsistent
with the objectives of the Zoning Code.
2. The strict or literal interpretations and enforcement of the specified regulation(s)
would deprive the applicant of privileges enjoyed by the owners of other properties
classified in the same zoning district.
Planning Commission Resolution No. 3703
PLN2005-145 -- 813 Cristich Lane -- Variance
Page 2
3. There are exceptional or extraordinary circumstances or conditions applicable to the
subject property (i.e. size, shape, topography) which do not apply generally to other
properties classified in the same zoning district.
4. The granting of the Variance will not constitute a grant of special privileges
inconsistent with the limitations on other properties classified in the same zoning
district.
5. The granting of the Variance will not be detrimental to the public health, safety, or
welfare, or materially injurious to properties or improvements in the area.
THEREFORE, BE IT RESOLVED that the Planning Commission grants a Variance
(PLN2005-145) to allow a building that was destroyed by fire to be re-built one foot from
a side property line on property owned by Mr. Howard Kaeding located at 813 Cristich
Lane in an M-1-S (Light Industrial) Zoning District.
PASSED AND ADOPTED this 13th day of December, 2005, by the following roll call
vote:
AYES:
NOES:
ABSENT:
ABSTAIN:
Commissioners:
Commissioners:
Commissioners:
Commissioners:
Alderete, Ebner, Francois, Gibbons and Roseberry
Doorley
None
Rocha
APPROVEO~~ Ufs~
ab Gibbons, Chair
ATTES~~ ~
Sharon Fierro, Secretary
-
,
~~.o~. C%.p(9)
t: ~
U r-
o 0
.... -'-
-s.~ ~
. (,
Ol/CH""O'
ITEM NO.4
CITY OF CAMPBELL' PLANNING COMMISSION
Staff Report. December 13, 2005
PLN2005-144
PLN2005-145
Kaeding, Inc.
Public Hearing to consider the application of Brent Kaeding, on behalf of
Kaeding Performance, for a Variance (PLN2004-145) and a Site and
Architectural Review (PLN2005-144) to allow to construction of a
warehouse/industrial building on property owned by Dixie and Howard
Kaeding located at 813 Cristich Lane in a M-I-S (Light Industrial) Zoning
District.
STAFF RECOMMENDATION
That the Planning Commission takes the following action:
I. Adopt a Resolution, incorporating the attached findings, denying a Variance to construct a
warehouselindustrial building with a reduced south side yard setback.
2. Adopt a Resolution, incorporating the attached findings, approving a Site and Architectural
Review Permit to construct a warehouse/industrial building, subject to the attached conditions of
approval.
ENVIRONMENTAL DETERMINATION
Staff recommends that the Planning Commission find that this project is Categorically Exempt
under Section 15303(c), of the California Environmental Quality Act (CEQA), pertaining to New
Construction of Small Structures.
PROJECT DATA
Net Lot Area:
18,386 gross sq. ft. (0.42 acres)
14,888 net square feet (0.34 acres)
Proposed Building Area:
SaleslDistribution Area:
Warehouse Area:
Total:
1,716 sq. ft.
3.631 sq. ft.
5,347 sq. ft.
Site Utilization:
Building Coverage:
Landscape Coverage:
Paving Coverage:
4,918 sq. ft. (33%)
1,956 sq. ft. (13%)
8,014 sq. ft. (54%)
Staff Report - Planning CC)lumission Meeting of December 13,200,
PLN2005-144/145 - 813 Cristich Lane
Page 2 of 7
FAR:
Allowable:
Proposed:
.40 maximum
.36
Height:
Allowable:
Proposed:
45' -0" feet maximum
24' -6"
Parking:
Required:
Provided:
(16) spaces (1 per 350 sq. ft. @ 5,347 sq. ft.)
(16) total spaces (one of which is accessible)
Hours of Operation:
Monday-Friday
Saturday-Sunday:
8:00 a.m. to 5:00 p.m.
closed
Adjacent Land Uses:
North:
South:
East:
West:
Industrial
Industrial
Industrial
Highway 17
BACKGROUND
The project site (and the two adjacent properties to the north) is home to Kaeding Performance, a
supplier of high performance race car parts. Kaeding Performance has operated their business from
this location for several decades. A fire, originating on the CalTrans property to the west, recently
destroyed a non-permitted industrial building on these sites. The remnants of this building were
demolished.
The building cannot be simply replaced under the provisions of the Nonconforming Structures
regulations for the following reasons: (1) the building was erected without permits and did not
comply with building and fire codes; (2) the building was demolished; and; (3) the restoration cost
exceeded 75% of the cost of construction of a comparable new structure. The building, therefore,
does not qualify as a nonconforming structure which could be replaced with a building permit only.
Preliminary Review of the proposed project was completed on September 22, 2005. Staff noted at
that time that a Variance for a reduced side yard setback cannot be supported by staff given that not
all variance findings could be made.
PROPOSAL
The applicant is requesting approval of a Site and Architectural Review and Variance to demolish
an existing residence, and construct a 5,347 square foot industrial building with a one foot south
-
Staff Report - Planning COlumission Meeting of December 13, 200~
PLN2005-144/145 - 813 Cristich Lane
Page 3 of 7
side yard setback where a 12'-3" (one-half the building height) side yard is required. The proposed
building is one-story with a mezzanine. The first floor includes 1,287 square feet ofretaiVsales and
3,631 square feet of warehouse. The second floor is a 429 square foot office space. The primary,
proposed use is warehouse, with secondary sales/distribution, of parts for high performance race
cars, and does not include automotive work.
Site improvements include (16) parking spaces (one of which is accessible) with one tree well, a
twenty foot wide landscaping strip in the front yard, a five foot wide landscaping strip along the
north property line, and a trash enclosure (at the rear of the site). The applicant added a six foot
high masonry wall along the west property line to screen view of the site from Highway 17 as
requested by staff.
The architectural design of the building has undergone several reVISIons. The building was
originally submitted as split-face block in two textures with no variation to the elevation faces or
height, with dark gray/green window frames and doors. The Project Plans presented this evening
now include both vertical and horizontal articulation to the elevations, a cornice cap, and a stucco
exterior in two shades of tan, with taupe trim and storefront mullions. The proposed man doors and
roll-up doors are specified as the same paint color as the surrounding body color (one of the two tan
shades).
Additional components of the project include a Lot Line Adjustment with the adjacent parcel to the
north to add a five foot strip of land with the project parcel, a ten foot dedication for additional
Cristich Lane right-of-way and a ten foot wide utility easement along the new east property line
(after the right-of-way dedication). Signs (a building sign and a monument sign in the front yard)
are shown as future, and are not being considered as a part ofthis application.
PROJECT SITE
The subject property is located on the west side of Cristich Lane. The property is surrounded by
commercial, industrial and residential uses. The site is currently improved with one, existing
nonconforming residence that was not damaged by the fire.
The project site is located in an M-l (Light Industrial) Zoning District, and is shown as a Light
Industrial land use designation on the General Plan.
ANALYSIS
General Plan Designation:
The General Plan land use designation for the project site is Light Industrial which permits
industrial uses. The primary, proposed use is warehousing which is consistent with the General Plan
Land Use Designation.
Zoning Designation:
The zoning designation for the project site is Light Industrial ("M-l"). The primary, proposed use
is warehousing which is a Permitted Use in the M-l zoning district. The secondary use, sales of
parts, is more incidental. Given the specialty nature of the product (high performance race car
Staff Report - Planning COlamission Meeting of December 13,200)
PLN2005-144/145 - 813 Cristich Lane
Page 4 of 7
parts), the proposed "sales" function acts more as a "distribution facility". Other Permitted Uses
allowed in the M-l zoning district include, for example, blueprinting shops. This type of facility
would include a sales component as well.
Required Entitlements:
The proposal to construct an industrial building requires Site and Architectural Review for the
design of the building and the layout of the site, a Variance to reduce one (south) required side yard
setback, and completion of a Lot Line Adjustment.
Site & Architectural Design & Performance:
The Campbell Municipal Code (CMC) regulates site development and performance standards for
industrial properties. As proposed, the project complies with all Zoning regulations except the
following:
· Section 21.10.080, Table 2-13, General Development Standards - M-l Zoning
District: The required side yard setback in the M-l zoning district is five feet or
one-half the height of the building wall adjacent to the side property line (whichever
is greater). The proposed south side yard setback is one foot. A reduced side yard
setback would therefore require a Variance.
· Section 21.26.020.D, Landscaping Requirements for M-l: A minimum 5-foot
planter strip is required along abutting property lines. The south property line is not
landscaped as the proposed setback is one foot.
Variance:
Given that the proposed project does not meet the above referenced code requirements, a Variance
is required. Campbell Municipal Code Section 21.48.040.B, Variance Findings, requires that the
following five specific findings be made in order to approve a Variance: (1) Hardship inconsistent
with the objectives of the Zoning Code; (2) Equal privileges; (3) Exceptional circumstances; (4) No
grant of special privilege; and, (5) No detriment to public health, safety or welfare; or property. A
full discussion of these findings is included in Attachment 1. There are no exceptional or
extraordinary circumstances or conditions applicable to the subject property (i.e. size, shape,
topography) which do not apply generally to other properties classified in the same zoning district.
Staff therefore recommends denial of the Variance, and revision of the project to comply with the
required side yard setback.
General Plan Consistency:
The Campbell General Plan sets forth policies and strategies for industrial neighborhoods.
As proposed, the project accomplishes the following:
· Policy LUT-5.4, Industrial Neil!hborhoods: Safeguard industry's ability to operate
effectively, by limiting the establishment of incompatible uses in industrial
Staff Report - Planning COIumission Meeting of December 13, 2005
PLN2005-144/145 - 813 Cristich Lane
Page 5 of 7
neighborhoods and encouraging compatible uses. The project advances this policy
by eliminating the nonconforming residence on site and constructing an industrial
building which meets current fire and buildings codes.
· Strategy LUT -5.4c, RedeveloDment: Facilitate redevelopment opportunity if the
McGlincy Lane Area. The project advances this strategy by complete redevelopment
of the site consistent with current design standards.
· Strategy LUT-5.6c, Physical Buffers: Provide landscaped buffers, sidewalks and
equipment screening to provide a visual and noise-abating buffer between uses. The
project advances this strategy by providing landscaping along the north side yard,
and a masonry trash enclosure in the rear.
· Strategy LUT-5.7a, Industrial Guidelines: Enhance the street frontage of a
building with landscaping and an emphasis on the office portion of the building. The
project advances this strategy by providing front yard landscaping, and by placing
the office and retail uses in the front of the building and the warehouse use in the
rear of the building.
· Strategy LUT-5.7c, Screenine:: Screen the service portion of industrial buildings
such as outdoor storage, trash enclosures and loading areas, especially those adjacent
to roadways or public amenities, with extensive landscaping and architectural
elements. The project advances this strategy by providing landscaping in the front
yard, a trash enclosure at the rear of the property, and a masonry wall along the
west property line abutting Highway 17.
· Policy LUT-5.8, Non-conformine: Uses: Encourage non-conforming properties to
redevelop as conforming uses. The project advances this policy by eliminating the
nonconforming residence on site and redeveloping the site with solely an industrial
use.
· Strategy LUT-5.7a, Industrial Guidelines: Require varied, high-quality, finished
construction materials such as glass, stucco, plaster, or brick. No exposed concrete
block or flat sheet metal. The proposed exterior finish, stucco, is consistent with this
guideline.
Site and Architectural Review:
As discussed above in the Project Proposal section, the project has undergone several architectural
revisions. Positive attributes of the project architecture include: articulated building elevations, a
stucco exterior, and screening (i.e., a masonry trash enclosure located at the rear of the site, a
parapet to screen all roof-top equipment, roll-up doors located off of the front elevation view, and a
six foot high masonry wall along the Highway 17 frontage). The masonry wall along the west
property line will greatly improve the view shed from Highway 17 as this property, which is located
Staff Report - Planning Corumission Meeting of December 13,2005
PLN2005-144/145 - 813 Cristich Lane
Page 6 of 7
upslope of the highway, is very visible and has no screening. There is currently no fence along the
west property line and the fire destroyed any vegetative screening which previously existed.
The Site Plan, however, has not changed. Staff meet with the applicant and the project architect
several times and requested a site plan which conforms with the zoning code (i.e., conforming south
side yard setback and landscaping), but the applicant wished to continue with processing of the
Variance. Positive attributes of the site plan include: front and north side yard landscaping, two-
way circulation, sufficient parking and loading areas, and the dedication of right-of-way for street
widening.
SITE AND ARCHITECTURAL REVIEW COMMMITTEE
The Site and Architectural Review Committee reviewed this application at its meeting of November
16, 2005. The Committee supported staff recommendation for the specification of an exterior
material which is recommended by the General Plan for Industrial properties. These changes have
been made by the applicant and are reflected on the Project Plans. The specified exterior material
was changed from split-face block to stucco, and additional building articulation was added. The
Committee did not feel that requiring a greater south side setback than proposed by the applicant
would benefit this project.
STAFF RECOMMENDATION
Staff recommends approval of the Site and Architectural Review, subject to conditions. Staff cannot
support the Variance, however, as there are no exceptional or extraordinary circumstances or
conditions applicable to the subject property, findings which is required for approval of a Variance.
Staff is, however, in the process of compiling a Zoning Code Update to address a number of code
revisions. As a part of this Update, staff is reviewing the development and performance standards
which are applicable to the Light Industrial zoning district as mandated by the policies and strategies
set forth in the Land Use and Transportation Element of the General Plan. Staff met with the
applicant and his architect after the Variance application was submitted to discuss the difficulties
associated with making the Variance findings. It was the decision of the applicant to continue
pursuing approval of a Variance.
If the Planning Commission is supportive of the Site and Architectural Review, staff would
recommend the following project-specific Conditions of Approval:
1. Provide the required south side yard setback;
2. Provide the required south side yard landscaping;
3. Provide a detailed Landscape Plan (species and sizes); and,
4. Submit the material and finish details for the fencing, walls, and trash enclosure.
These conditions are intended to improve the condition and appearance of the property from
Cristich Lane, and to provide compliance with the Zoning Code thereby eliminating the requirement
for a Variance.
Staff Report - Planning COlumission Meeting of December 13,2005
PLN2005-144/145 - 813 Cristich Lane
Page 7 of 7
Attachments:
1. Findings for Denial of the Variance (PLN2005-145)
2. Findings for Approval of the Site & Architectural Review (PLN2005-144)
3. Conditions of Approval for the Site & Architectural Review (pLN2005-144)
4. Letter from Applicant
5. Project Plans (Site Plan, Floor Plan, Elevations, and Photos)
6. Location Map
Prepared by:
Approved by:
S aron Fierro, Community Development Director
Attachment # 1
FINDINGS FOR DENIAL OF FILE NO. PLN2005-145
SITE ADDRESS:
APPLICANT:
DATE:
813 Cristich Lane
Brent Kaeding, on behalf of Kaeding Performance
December 13, 2005
Findings for denial of a Variance to reduce the south side yard setback for a
warehouse/industrial building at 813 Cristich Lane.
The Planning Commission finds as follows with regard to File No. PLN2005-145:
1. The proposed project consists of the demolition of an existing residence and the construction
of a new, 8,014 square foot warehouse/industrial building on a site where a previous
industrial building was destroyed by fire.
2. The proposed building is 5,347 square feet (including a 420 square foot mezzanine), and the
parcel is 14,888 net square feet in area. The Floor Area Ratio (FAR) of the proposed
building is .36, where a maximum of .40 is allowable. The height of the proposed building is
24' -6", where a maximum of 45'-0" is allowable. The proposed landscape cover is 13%,
where a minimum of 8% is required.
3. The proposed siting of the building would require approval of a Variance to reduce the south
side yard setback from 12'-3" to 1 '-0". The required side yard setback in the M-l zoning
district is 5 feet, or one-half the height if the building wall adjacent to the side property line,
whichever is greater. The building height is 24'-6", therefore the minimum, required side
yard setback is 12'-3".
4. Alternative site layouts and/or building footprints/massing could accommodate a building of
the same square footage on the subject property, and meet the required south side yard
setback.
5. Although other buildings in the McGlincy/Cristich neighborhood exist at lesser side yard
setbacks, these setbacks are nonconforming. In the event that any neighboring,
nonconforming structure was to be damaged or destroyed to the extent that the cost to repair
exceeded 75 percent (as is the case with the subject property), Campbell Municipal Section
21.58.050.E states that nonconforming rights are lost. This regulation applies equally to all
properties, thereby requiring conformity with current regulations when this level of damage
occurs.
6. The subject property is comparable in size with other properties located on the west and east
sides of South McGlincy and Cristich Lanes, therefore, there are no exceptional or
extraordinary circumstances or conditions applicable to the subject property (i.e. size, shape,
topography) which do not apply generally to other properties located in this neighborhood
and classified in the same zoning district.
Findings for Denial ofPLl~2005-145
813 Cristich Lane - Variance
Attachment # I
Page 2 of2
7. Given that the regulations regarding nonconforming properties apply equally to all properties
and that there are no exceptional or extraordinary circumstances or conditions applicable to
the subject property, the granting of a Variance for the south side yard setback will constitute
a grant of special privileges inconsistent with the limitations on other properties classified in
the same zoning district.
8. In general, the granting of the requested Variance would not be detrimental to the public
health, safety, or welfare, or materially injurious to properties or improvements in the area,
although the requested side yard setback reduction would eliminate the possibility of
landscape screening between adjoining properties as required by the zoning district standards.
Based upon the foregoing findings of fact, the Planning Commission further finds and concludes
that:
1. The strict or literal interpretations and enforcement of the specified regulation(s) would not
result in a practical difficulty or unnecessary physical hardship inconsistent with the
objectives of the Zoning Code.
2. The strict or literal interpretations and enforcement of the specified regulation(s) would not
deprive the applicant of privileges enjoyed by the owners of other properties classified in the
same zoning district.
3. There are no exceptional or extraordinary circumstances or conditions applicable to the
subject property (i.e. size, shape, topography) which do not apply generally to other
properties classified in the same zoning district.
4. The granting of the Variance will constitute a grant of special privileges inconsistent with the
limitations on other properties classified in the same zoning district.
5. The granting of the Variance will not be detrimental to the public health, safety, or welfare,
or materially injurious to properties or improvements in the area.
Attachment #2
RECOMMENDED FINDINGS FOR APPROVAL OF FILE NO. PLN2005-144
SITE ADDRESS:
APPLICANT:
P.C. MEETING:
813 Cristich Lane
Brent Kaeding for Kaeding Performance
December 13,2005
Findings for approval of a Site and Architectural Review Permit to construct a
warehouse/industrial building at 813 Cristich Lane.
The Planning Commission finds as follows with regard to File No. PLN2005-144:
I. The project is consistent with the development standards and design guidelines set forth in
the General Plan in that project eliminates a nonconforming residence, redevelops a site in
the McGlincy neighborhood, provides landscaping and screening, and utilizes high-quality,
finished construction materials.
2. Subject to compliance with conditions of approval requiring a conforming south side yard
setback and landscape buffer, the proposed project is consistent with the development
standards prescribed for the M-l (Light Industrial) Zoning District (i.e. minimum setbacks,
height restriction, floor area ratio, and parking requirements).
3. The project consists of a 5,347 square foot warehouse/industrial building, with a Floor Area
Ratio of 0.36, where the maximum floor area ratio is 0.40.
4. The project provides sixteen parking spaces where a minimum of sixteen parking spaces are
required.
5. The proposed project as conditioned is well designed and is architecturally compatible with
the surrounding neighborhood, and with the redevelopment expectations prescribed by the
General Plan. The building is well articulated and considers the design of all elevations, with
particular attention to the Cristich Lane streetscape and the view shed from Highway 17.
6. The proposed project does not include the removal of any protected trees.
7. The proposed project is surrounded by industrial to the north, south and east; and Highway 17
to the west.
8. The project qualifies as Categorically Exempt under Section 15303(c) of the California
Environmental Quality Act (CEQA), pertaining to New Construction of Small Structures in
an urbanized area.
Based upon the foregoing findings of fact, the Planning Commission further finds and concludes
that:
Findings for Approval of 1 LN2005-144
Site and Architectural Review Permit - 813 Cristich Lane
Attachment #2
Page 2 of2
1. The development will be compatible with the General Plan of the City and will aid in the
harmonious development of the immediate area.
2. The development will be compatible with the Zoning Code of the City.
3. No substantial evidence has been presented from which a reasonable argument could be made
that shows that the project, as currently presented and subject to the required conditions of
approval, will have a significant adverse impact on the environment.
4. The proposed development will not be detrimental to the health, safety or welfare of the
neighborhood or the City as a whole.
5. There is a reasonable relationship between the use of the fees imposed upon the project and
the type of development project.
6. There is a reasonable relationship and a rough proportionality between the conditions of
approval and the impacts of the project.
Attachment #3
CONDITIONS OF APPROVAL FOR FILE NO. PLN2004-144
SITE ADDRESS:
APPLICANT:
DATE:
813 Cristich Lane
Brent Kaeding for Kaeding Performance
December 13,2005
The applicant is hereby notified, as part of this application, that (s)he is required to meet the
following conditions in accordance with the ordinances of the City of Campbell and the State of
California. The lead department with which the applicant will work is identified on each
condition where necessary. Where approval by the Director of Community Development, City
Engineer, Public Works Director, City Attorney, or Fire Department is required, that review shall
be for compliance with all applicable conditions of approval, adopted policies and guidelines,
ordinances, laws and regulations, and accepted engineering practices, for the items under review.
Additionally, the applicant is hereby notified that (s)he is required to comply with all applicable
Codes or Ordinances of the City of Campbell and the State of California that pertains to this
development and are not herein specified:
COMMUNITY DEVELOPMENT DEPARTMENT
Plannine: Division:
1. Approved Proiect: Approval is granted for a Site & Architectural Review (PLN2004-144) to
construct a warehouse/industrial building at 813 Cristich Lane. The proposed project shall
substantially conform to the project exhibits listed below, except as may be modified by the
Conditions of Approval herein:
a. Set of plans prepared by LPMD Architects, received on December 5, 2005, including
building site and landscape plan, floor plans and roof plan, elevations and preliminary
grading and drainage, with the following revisions:
1. Provide all setbacks in conformance with the zoning code (i.e, increase the south
side yard setback to one-halfthe building height); and,
ii. Add minimum 5-foot planter strips along abutting property lines.
b. Color samples submitted by LPMD Architects, received on December 5,2005.
2. Site & Architectural Review Modification: Site and architectural plans, revised according to
Condition No.1, shall be reviewed and acted upon by the Site and Architectural Review
Committee if the revised plans substantially comply with the project submitted. If the revised
plans are not in substantial conformance, the plans shall return to the Planning Commission
for review and decision. The determination of substantial compliance shall be at the
discretion ofthe Community Development Director.
Conditions of Approval- rLN2005-144
Site and Architectural Review Pennit - 813 Cristich Lane
Attachment #3
Page 2 of8
3. Site & Architectural Review Approval Expiration: The Site & Architectural approval shall
be valid for one year from the date of final approval. Within this one-year period a building
permit must be obtained and construction completed one year thereafter, or the Site &
Architectural Review shall be void.
4. Revocation of Permit: The approved, primary use is a warehouse for parts for high
performance race cars. Given the specialty nature of the product, the on site "sales" function
more as "distribution". No auto repair, fabrication, finishing, assembly, augmentation, etc. is
approved for this site. Changes to the approved use require review and approval by the
Planning Commission. Operation of the use in violation of the Site and Architectural Review
or any standards, codes, or ordinances of the City of Campbell shall be grounds for
consideration of revocation of the Site and Architectural Review by the Planning
Commission.
5. Fencing. Walls and Trash Enclosure: All new fencing/walls shall comply with Section
21.18.060 of the Campbell Municipal Code. The design of, and the materials and colors for
the fencing, walls and trash enclosure shall be reviewed and approved by the Community
Development Director prior to issuance of a building permit.
6. Signage: No signage is approved as part of the development applications approved herein.
No sign shall be installed until a Sign Permit is approved as specified in the Sign Ordinance.
7. Parking and Driveways: All parking and driveway areas shall be developed in compliance
with the approved plans and Chapter 21.28 (parking and Loading) ofthe Campbell Municipal
Code.
8. On-Site Lighting: On-site lighting shall be shielded away from adjacent properties and
directed on site. The design, type, intensity and location of any proposed exterior lighting for
the project shall be reviewed and approved by the Community Development Director prior to
installation of the lighting for compliance with all applicable Conditions of Approval,
ordinances, laws and regulations. Lighting fixtures shall be of a decorative design to be
compatible with the industrial development and shall incorporate energy saving features.
9. Landscape Plan: Prior to the issuance of building permits, the applicant shall submit a final
detailed landscape and irrigation plan to the Planning Division for review and approval by the
Community Development Director. The landscape and irrigation plan shall substantially
confonn to the approved conceptual landscape plan and the City's Water Efficient
Landscaping Standards (WELS).
· All landscaping and trees shall be installed prior to the issuance of a Certificate of
Occupancy for the building.
· Minimum tree size of 15 gallon trees shall be provided.
Conditions of Approval - ~)I(e and Architectural Review Permit
PLN2004-144 - 813 Cristich Lane
Attachment #3
Page 3 of8
10. Utilities: All new on-site utilities shall be installed underground per section 21.18.140 of the
Campbell Municipal Code.
11. Screening: Screening of all roof-top equipment shall be shown on the plans submitted for a
building permit with a building cross section. The placement on site of any required utility
equipment (i.e., back-flow preventors, transformers, etc.) shall be reviewed and approved by
the Community Development Director prior to issuance of a building permit.
12. Paint Color: The approved paint colors shall be field-verified by the Community
Development Director.
13. Contractor Contact Information Posting: The project site shall be posted with the name and
contact number of the lead contractor in a location visible from the public street prior to the
issuance of building permits.
14. Construction Hours: Construction activities will be limited to the hours of 8:00 a.m. to 5:00
p.m. weekdays and 9:00 a.m. to 4:00 p.m. Saturdays. Construction is prohibited on Sundays
and Holidays, unless an exception is granted by the Building Official.
15. Hours: Construction activities will be limited to the hours of8:00 a.m. to 5:00 p.m. weekdays
and 9:00 a.m. to 4:00 p.m. Saturdays. Construction is prohibited on Sundays and Holidays,
unless an exception is granted by the Building Official.
16. Prooerty Maintenance: The property is to be maintained free of any combustible trash, debris
and weeds until the time that actual construction commences. All existing structures shall be
secured by having the windows boarded up and doors sealed shut, or shall be demolished or
removed from the property (Section 11.20 I and 11.414, 1985 Ed. Uniform Building Code).
17. Outdoor Storage: No outdoor storage or outdoor overnight parking is permitted on the
subject property. No equipment, materials or business vehicles shall be parked and/or stored
outside the building or within the parking lot.
18. Outdoor Display: No outdoor display is permitted on the subject property. All stock for sale
shall be kept and displayed inside the buildings. All exterior parking spaces shall be used
only for employees and/or customer use.
19. Building Modifications: Prior to any changes or modifications to the building or floor plan
the applicant shall submit proposed plans to the Community Development Department for
review an approval.
BuUdini! Division:
20. Permits Reauired: A building permit application shall be required for the proposed new
commercial structure. The building permit shall include Electrical/Plumbing/Mechanical
fees when such work is part of the permit.
Conditions of Approval - ~Ite and Architectural Review Permit
PLN2004-144 - 813 Cristich Lane
Attachment #3
Page 4 of8
21. Construction Plans: The Conditions of Approval shall be stated in full on the cover sheet of
construction plans submitted for building permit.
22. Size of Plans: The minimum size of construction plans submitted for building permits shall
be 24 in. by 36 in.
23. Plan Preparation: This project requires plans prepared under the direction and oversight of a
California licensed Engineer or Architect. Plans submitted for building permits shall be ''wet
stamped" and signed by the qualifying professional person.
24. Site Plan: Application for building permit shall include a competent site plan that identifies
property and proposed structures with dimensions and elevations as appropriate. Site plan
shall also include site drainage details. Site address and parcel numbers shall also be clearly
called out. Site parking and path of travel to public sidewalks shall be detailed. Site plan
shall also clearly call out location of a permanent elevation bench mark.
25. Soils Revort: Two copies of a current soils report, prepared to the satisfaction of the
Building Official, containing foundation and retaining wall design recommendations shall be
submitted with the building permit application. This report shall be prepared by a licensed
engineer specializing in soils mechanics.
26. Foundation Inspections: A pad certificate prepared by a licensed civil engineer or land
surveyor shall be submitted to the project building inspector upon foundation inspection.
This certificate shall certify compliance with the recommendations as specified in the soils
report and the building pad elevation and on-site retaining wall locations and elevations are
prepared according to approved plans. Horizontal and vertical controls shall be set and
certified by a licensed surveyor or registered civil engineer for the following items:
a. pad elevation
b. finish floor elevation (first floor)
c. foundation comer locations
27. Title 24 Energy Comoliance: California Title 24 Energy Standards Compliance forms shall
be blue-lined on the construction plans. Compliance with the Standards shall be
demonstrated for conditioning ofthe building envelope and lighting ofthe building.
28. Soecial Inspections: When a special inspection is required by V.B.C. Section 1701, the
architect or engineer of record shall prepare an inspection program that shall be submitted to
the Building Official for approval prior to issuance of the building permits, in accordance
with V.B.C Section 106.3.5. Please obtain City of Campbell, Special Inspection forms from
the Building Inspection Division Counter.
Conditions of Approval - ~lte and Architectural Review Permit
PLN2004-144 - 813 Cristich Lane
Attachment #3
Page 5 of8
29. Stormwater: The City of Campbell, standard Santa Clara Valley Non-point Source Pollution
Control Program specification sheet shall be part of plan submittal. The specification sheet
(size 24" X 36") is available at the Building Division service counter.
30. Title 24 Accessibility - Commercial: On site general path of travel shall comply with the
latest California Title 24 Accessibility Standards. Work shall include but not be limited to
accessibility to building entrances from parking facilities and sidewalks.
31. Title 24 Accessibility - Commercial: Projects seeking to use the Title 24 Hardship
exemption clause shall blue-line completed, City of Campbell "20%" exemption form on
submitted construction plans. Form is available at Building Division service counter.
32. Approvals Required: The project requires the following agency approval prior to issuance of
the building permit:
a. West Valley Sanitation District
b. Santa Clara County Fire Department
c. School District:
i) Campbell Union School District (378-3405)
ii) Campbell Union High School District (371-0960)
iii) Moreland School District (874-2900)
iv) Cambrian School District (377-2103)
d. Bay Area Air Quality Management District (Demolitions Only)
33. P. G.& E.: Applicant is advised to contact Pacific Gas and Electric Company as early as
possible in the approval process. Service installations, changes and/or relocations may
require substantial scheduling time and can cause significant delays in the approval process.
Applicant should also consult with P.G. and E. concerning utility easements, distribution pole
locations and required conductor clearances.
FIRE DEPARTMENT
34. Required Fire Flow: The fire flow for this project is 2,000 gpm at 20 psi residual pressure.
The adjusted fire flow is available from area water mains and fire hydrant(s) which are
spaced at the required spacing.
35. Fire Apoaratus (Engine) Access Roads Required: Provide access roadways with a paved all
weather surface, a minimum unobstructed width of 20 feet, vertical clearance of 13 feet 6
inches, minimum circulating turning radius of 36 feet outside and 23 feet inside, and a
maximum slope of 15%. Installations shall conform with Fire Department Standard Details
and Specifications sheet A-I.
36. Fire Lane Marking Required: Provide marking for all roadways within the project. Markings
shall be per fire department specifications. Installations shall also conform to Local
Government Standards and Fire Department Standard Details and Specifications A-6.
Conditions of Approval - ~lte and Architectural Review Permit
PLN2004-144 - 813 Cristich Lane
Attachment #3
Page 6 of8
PUBLIC WORKS DEPARTMENT
37. Legal Lot: The applicant shall provide documentation to ascertain that the property has been
legally created.
38. Preliminary Title Report: Prior to issuance of any grading or building permits for the site, the
applicant shall provide a current Preliminary Title Report.
39. Irrevocable Offer of Dedication for Public Street Purposes: Prior to issuance of any grading
or building permits for the site, the applicant shall make an irrevocable offer of dedication in
fee simple for additional right-of-way for public street purposes along the Cristich Lane
frontage to accommodate a 30 foot half street width and a 10 foot Public Utility Easement.
The applicant shall submit the necessary documents for approval by the City Engineer,
process the submittal with City staffs comments and fully complete the right-of-way process.
The applicant shall cause all documents to be prepared by a registered civil engineer/land
surveyor, as necessary, for the City's review and recordation.
40. Deferred Street Imorovement Agreement: Prior to issuance of any grading, drainage, or
building permits for the site, the owner shall execute a deferred street improvement
agreement for construction of standard street improvements, as required by the City Engineer.
The future plans for the deferred street improvement shall include the following:
a. Show location of all existing utilities within the new and existing public right of way.
b. Relocation of all existing utilities including utility boxes, covers, poles, etc. outside of
sidewalk area. No utility boxes, covers, etc. will be allowed in the sidewalk area.
c. Removal of existing street section to centerline.
d. Installation of engineered structural pavement section to centerline, as required by the
City Engineer.
e. Installation of standard curb, gutter, sidewalk and ADA compliant driveway
approaches.
f. Installation of street trees, tree wells and irrigation at 30 feet on center.
g. Installation of streetlights, conduits, conductors and related facilities in accordance with
the City of Campbell's Street Lighting Policies.
h. Installation of traffic control, signage, and markings.
1. Construction of conforms to existing public and private improvements, as necessary.
41. Water Meter(s) and Sewer Cleanout(s): Existing and proposed water meter(s) and sewer
cleanout(s) shall be relocated or installed on private property behind the future public right-
of-way line.
42. Utilities: All on-site utilities shall be installed underground per Section 21.18.140 of the
Campbell Municipal Code for any new or remodeled buildings or additions. Applicant shall
comply with all plan submittals, permitting, and fee requirements of the serving utility
compames.
Conditions of Approval - ~lte and Architectural Review Permit
PLN2004-144 - 813 Cristich Lane
Attachment #3
Page 7 of8
43. Utility Coordination Plan: Prior to issuance of building permits for the site, the applicant
shall submit a utility coordination plan and schedule for approval by the City Engineer for
installation and/or abandonment of all utilities. The plan shall clearly show the location and
size of all existing utilities and the associated main lines; indicate which utilities and services
are to remain; which utilities and services are to be abandoned, and where new utilities and
services will be installed. Joint trenches for new utilities shall be used whenever possible.
44. Pavement Restoration: Based on the utility coordination plan, the applicant shall prepare a
pavement restoration plan for approval by the City Engineer prior to any utility installation or
abandonment. Public Streets that have been reconstructed or overlaid within the previous five
years will require boring and jacking for all new utility installations. Cristich Lane is
currently a private street.
45. Grading and Drainage Plan: Prior to issuance of any grading or building permits for the site,
the applicant shall conduct hydrology studies based on a ten-year storm frequency, prepare an
engineered grading and drainage plan, and pay fees required to obtain necessary grading
permits. The plans shall comply with the 1998 edition of the California Building Code
including Chapters 10, 11, 18,33, and Appendix Chapter 33.
46. Storm Drain Area Fee: Prior to issuance of any grading or building permits for the site, the
applicant shall pay the required Storm Drain Area fee, currently set at $2,650 per net acre,
which is $927.00.
47. Stormwater Pollution Prevention Measures: Prior to issuance of any grading or building
permits, the applicant shall comply with the National Pollution Discharge Elimination
System (NPDES) permit requirements, Santa Clara Valley Water District requirements, and
the Campbell Municipal Code regarding stormwater pollution prevention. Specifically the
project must include source control, site design and treatment measures to achieve
compliance with Provision C.3. of the NPDES Permit. Measures may include, but are not
limited to, minimization of impervious surface area, vegetated swales, infiltration areas, and
treatment devices. The primary objectives are to improve the quality and reduce the quantity
of stormwater runoff to the bay.
Resources to achieve these objectives include Storm water Best Management Practices
Handbook for New Development and Redevelopment ("CA BMP Handbook") by the
California Stormwater Quality Association (CASQA), 2003; Start at the Source: A Design
Guidance Manual for Stormwater Quality Protection ("Start at the Source") by the Bay Area
Stormwater Management Agencies Association (BASMAA), 1999; and Using Site Design
Techniques to Meet Development Standards for Storm water Quality: A Companion
Document to Start at the Source ("Using Site Design Techniques") by BASMAA, 2003.
a. Upon submission of the plans, the applicant shall calculate and submit to the City the
amount of impervious surface created or replaced by the development.
b. Upon submission of the grading and drainage plan, the applicant's designer or engineer
shall also submit the required certification for sizing, selection, and preliminary design of
Conditions of Approval - oJl(e and Architectural Review Permit
PLN2004-144 ~ 813 Cristich Lane
Attachment #3
Page 8 of8
treatment BMP's for the project site to meet the requirements of the City of Campbell's
NPDES permit, No. 01-119, Provision C.3.
c. The applicant shall also comply with any other or new conditions as required by the City
of Campbell's most current NPDES permit.
48. Operation and Maintenance of Stormwater Pollution Prevention Measures: Prior to issuance
of the building permit, the applicant shall execute an agreement and provide security for the
operation and maintenance of stormwater pollution prevention measures installed or provided
as a part ofthis project.
Prior to allowing occupancy for any and/or all buildings, the applicant shall:
a. Have a qualified BMP certifier inspect the stormwater management facilities, submit a
complete set of as-built drawings to Public Works Engineering, and certify on these
drawings that:
1. The stormwater management facilities were constructed in compliance with approved
plans;
11. The as-built drawings show all pertinent constructed dimensions, elevations, shapes,
and materials;
iii. All variations in construction from the approved design plan have been identified,
including omissions to and additions from the approved plan; and
iv. Any changes are in conformance with local, state, or federal regulations.
b. Sign the "Covenants for the Operation and Maintenance of Stormwater Facilities".
Attachment #4
LPM D Architects
2620 Augustine Dr. Suite 185, Santo Claro, CA 95054
October 10, 2005
Mr. Tim Haley
City of Campbell Planning Department
70 North First Street
Campbell, CA 95008
RE: Variance application for 813 Cristich Lane, Campbell
"Written Statement"
Dear Tim:
This variance application is submitted to your office with the following Written
Statement:
"The current site is in transition and redevelopment now due to a fire that initiated from
the State Highway property and extended up the into my clients property and destroyed
the structures that were part of his active business on this site. In order for the new
structure to maintain economic use of the property that is now required to meet current
Planning and Building Codes, the building location must be allowed to be constructed l'
off the southern property line. We feel this request for variance is compatible with the
existing developments along Cristich Lane where "0" setbacks along property lines are
prevalent. "
~ ;JYI
Debbie Hill
Principal of Projects
408-748-1847 phone
408-748-1849 fax
RECEIVED
OCT 1 1 2005
CITY OF CAMPBELL
PLANNING DEPT.